Eaton
10000 Woodward Avenue
Woodridge, Illinois 60517
+1 773-869-1776
+1 (773) 869-1329
cpdipresaleshelp@eaton.com
United States
Contact Us

Compare Products


DIN500AC

Eaton 500VA 300W 120V AC DIN Rail Industrial UPS - Hardwire Input/Output

More Info
How to Order
OVERVIEW
UPS Type
Standby
INPUT
Input Phase
Single-Phase
Rated input current (Maximum Load)
10A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
Hardwire
UPS Input Connection Description
Recommended 18 AWG 194°F(90°C) rated copper wire
Input Circuit Breakers
10A
Recommended Electrical Service
15A 120V
OUTPUT
Output Capacity (VA)
500
Output Capacity (kVA)
0.5
Output Capacity (Watts)
300
Output Capacity (kW)
0.3
Power Factor
0.6
Nominal Voltage Details
115v nominal output in battery mode
Frequency Compatibility
50 / 60 Hz
Frequency Compatibility Details
50 or 60Hz +/- 10% (Auto-sensing)
Output Voltage Regulation (Battery Mode)
+/- 5%
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
PWM sine wave
Nominal Output Voltage(s) Supported
120V
Output Receptacles
(1) Hardwire
Individually Controllable Load Banks
No
BATTERY
Battery Type
Valve Regulated Lead Acid (VRLA)
Runtime Full Load (min.)
4 min. (300W)
Runtime Half Load (min.)
14.5 min. (150W)
Expandable Runtime
No
DC System Voltage (VDC)
12
Battery Recharge Rate (Included Batteries)
1.5A Maximum; Less than 3 hours from 10% to 90%
Battery Access
Top-mounted battery access panel
Internal UPS Replacement Battery Cartridge
RBC12V9ET
USER INTERFACE, ALERTS & CONTROLS
Switches
Includes 1 on/off/test push button
Alarm Cancel Operation
Press and hold On/Off/Test button for 1 second
Audible Alarm
Yes
LED Indicators
ALARM - RED - Flashes when the battery needs to be recharged and tested. SOLID RED when the unit is subjected to an overload condition. YELLOW - ON SOLID when the UPS is supplying battery power to the loads. GREEN - ON SOLID GREEN when the line input voltage is normal.
SURGE / NOISE SUPPRESSION
EMI / RFI AC Noise Suppression
Yes
AC Suppression Joule Rating
558
PHYSICAL
Primary Form Factor
DIN-Rail
Cooling Method
Convection
UPS Housing Material
Steel
Unit Dimensions (hwd / in.)
5.220 x 12.280 x 5.500
Unit Weight (lbs.)
11.600
ENVIRONMENTAL
Operating Temperature Range
32° to 122°F (0° to 50°C)
Storage Temperature Range
5° to 122°F (-15° to 50°C)
Relative Humidity
0% to 95%, Non-Condensing
AC Mode BTU / Hr. (Full Load)
31
AC Mode Efficiency Rating (100% Load)
97%
Operating Elevation
0-10000 ft. (0-3000 m)
Audible Noise
40 dBA at 1 meter
COMMUNICATIONS
PowerAlert Software
PowerAlert Office
Communications Cable
USB 2.0 Cable
Network Management Card Description
Network management not supported
Communications Interface
(1) USB (HID enabled)
Emergency Power Off (EPO)/Remote On-Off (ROO)
Yes
LINE / BATTERY TRANSFER
Transfer Time
<8ms (Typical), 10ms (Max)
Low Voltage Transfer to Battery Power (Setpoint)
99V
High Voltage Transfer to Battery Power (Setpoint)
144V
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode During a Power Failure)
Cold Start operation supported
High Availability UPS Features
Surge/noise protection
Green Energy-Saving Features
High efficiency economy mode operation; Greater than 95% efficiency - GREEN UPS
APPLICATIONS
UPS Applications
Extreme Temperature Applications; Industrial
STANDARDS & COMPLIANCE
Product Certifications
CAN/CSA-C22.2 No. 107.3 (Canada); CSA (Canada); ICES (Canada); UL 1778; UL 508
Product Compliance
FCC Part 15 Class B (USA); RoHS
WARRANTY & SUPPORT
Product Warranty Period (Worldwide)
2-year limited warranty

Need help with your purchase?
We're always available to help with questions, including product selection, sizing, installation and product customization. Call us at +1 773-869-1776 or email cpdipresaleshelp@eaton.com.